首页> 外文会议>International Conference on Electronic Devices, Systems and Applications >The peculiarities of interruption of the medium voltage motors byVCB with CuCr contacts vacuum circuit breakers
【24h】

The peculiarities of interruption of the medium voltage motors byVCB with CuCr contacts vacuum circuit breakers

机译:用CUCR触点真空断路器的媒体电压电动机中断中断的特性真空断路器

获取原文

摘要

The Monte-Carlo simulation technique and appropriate software has been developed to analyze the switching overvoltages occurring at the interruption of 6 and 10 kV motors by vacuum circuit breakers (VCB) with CuCr contacts. VCB parameters have been determined experimentally. A comparison has been provided between VCB switching behaviour at the interruption of 6 and 10 kV motors. Voltage escalation has been shown to be the most important process for 6 kV motors with respect to switching overvoltages generation. In contrast to 6 kV motors, three-phase virtual current chopping predominates for 10 kV motors. It has been deducted that for the majority of the real field applications, the VCB with the most popular contact material (CuCr base) can create dangerous overvoltages. Switching surge analysis conducted with the aid of the Alternative Transients Program (ATP) proved a metal oxide surge arrester connected in parallel to VCB contacts to be the most effective way to suppress phase to ground overvoltages. Turn-to-turn overvoltages induced at interruption of medium voltage motors by VCB with the described protection have also been studied. These overvoltages have been compared with the turn-to-turn overvoltages induced by an “ideal” breaker that does not interrupt high frequency current at all. The authors' analysis revealed that the maximum turn-to-turn overvoltages induced by VCB with adequate protection do not exceed overvoltages induced by an “ideal” circuit breaker for more then 15% and are lower then similar overvoltages induced by conventional breakers under the same conditions
机译:已经开发了Monte-Carlo仿真技术和适当的软件,以通过具有CUCR触点的真空断路器(VCB)来分析在6和10 kV电动机中断发生的开关过电压。 VCB参数已经通过实验确定。在6和10 kV电机中断的VCB切换行为之间提供了比较。已经显示电压升级是6 kV电动机相对于切换过电压产生的最重要的过程。与6 kV电机相比,三相虚拟电流斩波10 kV电机。它已被扣除,对于大多数实地应用,VCB具有最流行的接触材料(CUCR基础)可以产生危险的过电压。借助于替代瞬变程序(ATP)进行切换浪涌分析证明了与VCB触点平行连接的金属氧化物浪涌避雷器,是抑制接地过电压的最有效的方法。还研究了通过VCB与所描述的保护的中间电压电机中断引起的转弯过电压。将这些过电压与由“理想”断路器引起的转弯过电压进行了比较,这些断路器根本不会中断高频电流。作者的分析显示,VCB具有足够保护的最大转向转向过电压不超过由“理想”断路器引起的过电压,然后再为15%而引起的,并且在相同的传统断路器下方均匀地引起的相似过电压条件

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号