Development of an open-loop ground source cooling system for space air conditioning system in hot climate like Indonesia

机译:在印度尼西亚等炎热气候空间空调系统开环地源冷却系统的开发

获取原文

摘要

Ground source cooling system (GSCS) is promising technology to serve cooling demands of buildings. This study presents a development of an open-loop GSCS for space air conditioning at Hasanuddin University Gowa campus. Experimental study was carried-out by pumping water from well of 57 m depth and flowing the water over a heat exchanger to cool refrigerant of air conditioning (AC) unit. The performance of AC unit was investigated under actual operation with various water flowrates. The temperatures of inlet and outlet water in the heat exchanger were also measured. The system operated from 11:00 until 18:00 o'clock local time with 3 (three) flowrates such as 3.6; 6.5 and 14.3 L/min respectively. In the low flowrate, the temperature of outlet water is approximately 37°C. However, the compressor power is also increase significantly. The coefficient of performances (COPs) of the system in average are 2.9 in the low flowrate and 3.4 in the high flowrate. Also. the result shows that the utilization of GSCS is appropriated for cooling buildings in the hot climate like Indonesia.
机译:地源冷却系统(GSCs)是有前途的技术,可提供建筑物的冷却需求。本研究提出了在Hasanuddin大学Gowa Campus的空间空调的开放式GSC的开发。通过从57米深度的井中泵送水并在热交换器上流过换热器以冷却空调(AC)单元的制冷剂进行实验研究。通过使用各种水流量进行实际操作来研究AC单元的性能。还测量了热交换器中的入口和出口水的温度。该系统从11:00到18:00点,当地时间为3(三个)流量,如3.6; 6.5和14.3 L / min。在低流量的情况下,出口水的温度约为37℃。但是,压缩机功率也显着增加。系统的性能系数(COP)平均为2.9,在低流量和高流量中为3.4。还。结果表明,GSC的利用是在印度尼西亚这样的热气氛中的冷却建筑物占用。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号