Energy use optimization in the building of National Library

机译:国家图书馆建设中的能源使用优化

获取原文

摘要

The analysis of inner climate parameters and energy use was carried out in the Krasinski Palace in Warsaw: seat of The Polish National Library. The building includes books stores, conservation workshops, reading rooms and offices. Central hydronic heating system and sporadically used local air dryers are the only active systems. The purpose of the analysis was to check at which extent actual microclimate and energy management can be improved. Several alternative scenarios, not compromising climatic protection level of valuable collections, to optimize energy use were elaborated. It turned out, that only improving of heating control and doubling of thermal insulation thickness of ceiling to attic allows for up to 30% of energy savings. Application of extended HVAC systems is not necessary due to high hygrothermal inertia of the building. WUFI~RPLUS software was used for the building simulations. The calculation model was first validated against energy use for heating and inner climate measurement results. A special module was used to account for moisture exchange between books and inner air.
机译:在华沙的Krasinski Palace中进行了内部气候参数和能源使用的分析:波兰国家图书馆的席位。该建筑包括书店,保护车间,阅览室和办公室。中央水性加热系统和散发使用的本地空气干燥器是唯一的活性系统。分析的目的是检查是否可以改善实际微气密和能源管理的程度。阐述了几种替代方案,而不是妥协的气候保护水平,以优化能源使用。事实证明,只有改善加热控制和天花板热绝缘厚度的加倍才能节省高达30%的能量。由于建筑物的高湿热惯性,不需要扩展HVAC系统的应用。 Wufi〜Rplus软件用于建筑模拟。首次验证计算模型以防止能量用途,用于加热和内部气候测量结果。使用特殊模块来解释书籍和内部空气之间的水分交换。