首页> 外文会议>International Conference on Electrical, Control and Automation Engineering >PD Detection on Power Cable with Peak-Correlation Method
【24h】

PD Detection on Power Cable with Peak-Correlation Method

机译:具有峰值相关方法电力电缆的PD检测

获取原文

摘要

Oscillating voltage is an effective method for PD detection in XLPE cable. In this paper, it mainly described the principle of oscillating waveform test system (OWTS) for PD detection and proposed the peak-correlation method for the location of partial discharge points. Then, an oscillating waveform test system for 10kV cable was established in the laboratory. It was used for the PD testing of a 500 meters long cable. In the end of the paper, the waveform characteristics of the direct pulse and reflect pulse were analyzed. With this feature, the problem caused by multi PDs in a single time window could be effectively solved which greatly improved the reliability and automation of the PD location algorithm. Experimental results show that oscillating voltage can effectively excite the generation of partial discharge and peak-correlation is a valid method for PD location with sufficient accuracy and reliability.
机译:振荡电压是XLPE电缆中PD检测的有效方法。在本文中,主要描述了对PD检测的振荡波形测试系统(OVTS)的原理,并提出了用于局部排出点的位置的峰值相关方法。然后,在实验室中建立了10kV电缆的振荡波形测试系统。它用于500米长的电缆的PD测试。在纸张的末尾,分析了直接脉冲的波形特性和反射脉冲。利用此特征,可以有效地解决了由单个时间窗口中的多PD引起的问题,这大大提高了PD位置算法的可靠性和自动化。实验结果表明,振荡电压可以有效激发局部放电的产生和峰值相关是PD位置的有效方法,具有足够的精度和可靠性。