FACILITY COOLING FAILURE ANALYSIS OF DIRECT LIQUID COOLING SYSTEM IN DATA CENTERS

机译:数据中心直接液体冷却系统的设施冷却故障分析

获取原文

摘要

This work experimentally studies the impact of facility cooling failure of a direct liquid cooling (DLC) system on the IT equipment (ITE). The facility side of a DLC system removes the heat from a secondary loop-in direct contact with the ITE- and discard it in a chiller loop or ambient. The CPU utilization and coolant set point temperature (SPT) are varied to understand the effect of failure under different operating conditions. The ITE response is studied in terms of chip temperature and power, and fan speed. It was found that failure of the facility cooling system is not hazardous to the IT operation. The rate of change in temperature after failure is low and is sufficient to turn the ITE off safely. This is attributed to the surrounding air in the data center and the thermal mass of the cooling system.
机译:这项工作实验研究了直接液体冷却(DLC)系统对IT设备(ITE)的设施冷却失效的影响。 DLC系统的设施侧从二级环路直接接触到ITE中的热量,并将其丢弃在冷却器环或环境中。 CPU利用率和冷却液设定点温度(SPT)可以变化以了解不同操作条件下的故障效果。在芯片温度和功率和风扇速度方面研究了ITE响应。发现设施冷却系统的故障对IT操作没有危险。故障后的温度变化率低,足以安全地关闭ite。这归因于数据中心的周围空气和冷却系统的热质量。