Failure Analysis of Direct Liquid Cooling System in Data Centers

机译:数据中心直接液体冷却系统的故障分析

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

In this paper, the impact of direct liquid cooling (DLC) system failure on the information technology (IT) equipment is studied experimentally. The main factors that are anticipated to affect the IT equipment response during failure are the central processing unit (CPU) utilization, coolant set point temperature (SPT), and the server type. These factors are varied experimentally and the IT equipment response is studied in terms of chip temperature and power, CPU utilization, and total server power. It was found that failure of this cooling system is hazardous and can lead to data center shutdown in less than a minute. Additionally, the CPU frequency throttling mechanism was found to be vital to understand the change in chip temperature, power, and utilization. Other mechanisms associated with high temperatures were also observed such as the leakage power and the fans' speed change. Finally, possible remedies are proposed to reduce the probability and the consequences of the cooling system failure.
机译:本文通过实验研究了直接液体冷却(DLC)系统故障对信息技术(IT)设备的影响。预计在故障期间会影响IT设备响应的主要因素是中央处理器(CPU)的利用率,冷却液设定点温度(SPT)和服务器类型。这些因素会根据实验进行变化,并根据芯片温度和功率,CPU利用率以及服务器总功率来研究IT设备的响应。发现该冷却系统的故障是危险的,并且可能导致数据中心在不到一分钟的时间内关闭。另外,发现CPU频率调节机制对于理解芯片温度,功率和利用率的变化至关重要。还观察到了与高温相关的其他机制,例如泄漏功率和风扇速度变化。最后,提出了可能的补救措施以减少冷却系统故障的可能性和后果。