A Harmonic Currents Compensation Strategy of Active Load Balancer With Constant DC-Capacitor Voltage Control on Three-Phase Four-Wire Distribution Feeders

机译:三相四线配电器恒定直流电压控制具有谐波电流的谐波电流补偿策略

获取原文

摘要

This paper deals with harmonic currents compensation strategy for Active Load Balancer (ALB) with constant dc-capacitor voltage control on three-phase four-wire distribution feeders. Only the constant dc-capacitor voltage control, which is commonly used in the active power line conditioners(APLCs), is used to compensate unbalanced active, reactive and harmonic currents on three-phase four-wire distribution feeders. Any calculation blocks of the active, reactive and harmonic components of the load currents are not needed. The basic principle of the constant dc-capacitor voltage control strategy for the ALB is discussed in detail. The instantaneous power flows into ALB shows that balanced and sinusoidal source currents with a unity power factor are achieved with the constant dc-capacitor voltage control based algorithm. The validity and high practicability of the proposed strategy are confirmed by digital computer simulation using PSIM software. Simulation results demonstrate that balanced and sinusoidal source-currents with a unity power factor are achieved using the proposed control algorithm.
机译:本文对三相四线配电馈线上具有恒定直流电压控制的主动负载平衡器(ALB)的谐波电流补偿策略。只有在有源电力线调节器(APLC)中常用的恒定DC电容电压控制,用于补偿三相四线分配馈线上的不平衡活性,无功和谐波电流。不需要负载电流的有效,无功和谐波分量的任何计算块。详细讨论了ALB的恒定DC电容器电压控制策略的基本原理。瞬时功率流入ALB,表明,利用恒定的DC电容器电压控制的算法实现了具有unity功率因数的平衡和正弦源电流。使用PSIM软件的数字计算机仿真确认了所提出的策略的有效性和高实用性。仿真结果表明,使用所提出的控制算法实现了具有单位功率因数的平衡和正弦源电流。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号