首页> 外文会议>International Symposium on Heating, Ventilation and Air Conditioning >The characteristics of the patient's requirement for the ward thermal environment
【24h】

The characteristics of the patient's requirement for the ward thermal environment

机译:病人对病房热环境要求的特点

获取原文

摘要

In order to create and evaluate the thermal environment in hospital wards, field experiments, including subjective surveys and field thermal environment tests, were conducted in 4 hospitals. A total of 778 effective data sets were obtained. The Predicted Mean Vote (PMV) of the seated patients were calculated according to Fanger's PMV thermal comfort model, and the PMV of the lying patients were calculated based on Lin & Deng's PMV thermal comfort model in sleeping environments. The thermal insulation values of bedding systems were calculated according to the heat transfer equation, and their health status were described and quantified by the EQ-5D health index. The characteristics of the patient's requirements of the thermal environment were analyzed, including neutral temperature, preferred temperature, 80% acceptable temperature etc. The logistic regression model of binomial classification shows that operative temperature, EQ-5D index, ward department and activity level had significant influence on the difference patients' thermal sensation.
机译:为了创建和评估在医院病房,现场实验,其中包括主观调查和现场热环境测试,热环境,在4家医院进行的。共获得的778个有效数据集。的坐在患者预测平均投票(PMV)根据范格的PMV热舒适模型计算,并躺在患者的PMV是基于在睡眠环境林和邓的PMV热舒适模型计算。床上用品系统的热绝缘值根据所述传热方程计算,并且由EQ-5D健康指数他们的健康状况进行了描述和量化。的热环境的患者的要求特性进行了分析,包括中性温度,优选的温度,80%可接受的温度等的二项式分类示出了逻辑回归模型,控制温度,EQ-5D指数,病房部和活动水平有显著在差异患者的热感觉影响。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号