首页> 外文会议>International Symposium on Heating, Ventilation and Air Conditioning >Effect of Thermal Plume on Personal Thermal Comfort in Displacement Ventilation at One Side of the Room
【24h】

Effect of Thermal Plume on Personal Thermal Comfort in Displacement Ventilation at One Side of the Room

机译:热羽流对房间一侧位移通风中个人热舒适度的影响

获取原文

摘要

The Indoor Zero-Equation Turbulence Model in software Airpak was adopted to simulate the personal thermal comfort in the condition of displacement ventilation at the left side. The parameters of the simulated environment were 25 "C and 40%. The simulated results show that over the person, there was a clear phenomenon of thermal plume which entrains the around air resulting in the decrease of the temperature with the increasing of the height. As for the. predicted mean vote (PMV) and the percent person's dissatisfied (PPD), their gradient were depended on the temperature distribution formed by thermal plume, and the average value was 0.249 for PMV and 7.25% for PPD. All these show that the effect of thermal plume can not be neglected in the design of HVAC system.
机译:采用软件Airpak中的室内零方程湍流模型来模拟左侧位移通风条件下的个人热舒适度。模拟环境的参数为25英寸C和40%。模拟结果表明,在该人上,热羽流明显现象,其夹带周围的空气,导致温度随着高度的增加而降低。至于。预测的平均投票(PMV)和百分比的人不满(PPD),它们的梯度依赖于热羽流形成的温度分布,PMV的平均值为0.249,PPD为7.25%。所有这些都显示出来在HVAC系统的设计中,热羽流不能忽视的效果。