首页> 外文会议>International Building Physics Conference >On decentralized air-conditioning for hot and humid climates: Performance characterization of a small capacity dedicated outdoor air system with built-in sensible and latent energy recovery wheels
【24h】

On decentralized air-conditioning for hot and humid climates: Performance characterization of a small capacity dedicated outdoor air system with built-in sensible and latent energy recovery wheels

机译:关于热潮湿气候的分散空调:小容量专用户外空气系统的性能表征,内置明智和潜能回收轮

获取原文

摘要

In large commercial buildings facing high cooling loads, conventional heating, ventilation, and air-conditioning (HVAC) systems are typically based on the use of one, or few, large-capacity air handling units (AHUs) to supply conditioned air throughout a centrally-managed air distribution network. The alternative concept of 'decentralized' HVAC typically entails the deployment of multiple, small capacity fan coil units (FCUs) operating as dedicated outdoor air systems (DOAS) and located closest to the individual thermal zones they must condition. For this study, the authors commissioned the development of a small capacity, packaged cooling coil with built-in enthalpy recovery devices. This customised unit, intended for use in a cooling-only, decentralized DOAS configuration, includes: two rotary wheels for sensible and latent energy recovery, a single cooling coil, and both supply and exhaust fans. The unit has been intended for building air conditioning use in the Singaporean climate. This paper provides energy performance data based on laboratory testing of the unit with independent control of the following variables: outdoor air conditions, return air conditions, and chilled water flow rate. It is intended that empirical data offered by this study can be adapted for use in future building energy models of decentralized HVAC systems.
机译:在面向高冷却载荷的大型商业建筑中,传统的加热,通风和空调(HVAC)系统通常基于使用一个或少数大容量的空气处理单元(Ahus)来在整个中央提供条件空气 - 营销空气分销网络。 “分散”HVAC的替代概念通常需要部署作为专用室外空气系统(DOA)的多个小容量风扇线圈单元(FCU),并位于它们必须条件的各个热带。对于这项研究,作者委托了一种小容量的开发,封装的冷却卷,内置焓恢复装置。这种定制单元,用于仅用于冷却的分散的DOAS配置,包括:两个旋转轮,用于明智的和潜能回收,单个冷却线圈和供应和排气扇。该单位旨在建立新加坡气候中的空调使用。本文提供了基于单位的实验室测试的能量性能数据,具有独立控制下列变量:室外空气条件,返回空气条件和冷水流速。本研究提供的经验数据旨在适用于分散的HVAC系统的未来建筑能源模型。

著录项

相似文献

  • 外文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号