首页> 外文会议>International Conerence on Applied Energy >1D model to predict ejector performance at critical and sub-critical operation in the refrigeration system
【24h】

1D model to predict ejector performance at critical and sub-critical operation in the refrigeration system

机译:1D模型预测制冷系统中临界和亚临界操作的喷射器性能

获取原文

摘要

A new 1D model using the real gas property is proposed to predict ejector performance at critical and sub-critical operational modes, while most previous 1D models usually used the ideal gas property and only predicted ejector performance at critical mode operation. Constant pressure mixing is assumed to occur inside the constant area section of the ejector at critical and sub-critical mode operation, and the effectiveness of the model is verified against experimental data. The results show that the proposed model accurately predicts ejector performance over all ranges of operation. The 1D model is a useful tool for predicting ejector performance within larger refrigeration cycle models.
机译:建议使用真实气体属性的新的1D模型以临界和亚临界操作模式预测喷射器性能,而最前面的1D型号通常使用理想的气体特性,并且仅在关键模式操作下仅预测的喷射器性能。假设恒定压力混合在弹射器的恒定区域部分内发生在临界和亚临界模式操作内,并且模型的有效性针对实验数据验证。结果表明,该模型精确地预测了所有操作范围的喷射器性能。 1D模型是一种有用的工具,用于预测喷射器性能在较大的制冷循环模型中。