首页> 外文会议>International Workshop on Materials Engineering and Computer Sciences >Study on Ferroresonance Elimination in 10kV Power Distribution System With 4TV Method
【24h】

Study on Ferroresonance Elimination in 10kV Power Distribution System With 4TV Method

机译:具有4TV法的10kV配电系统中铁谐波消除研究

获取原文

摘要

Distribution networks can emerge long-time over-voltage due to ferroresonance caused by the electromagnetic voltage transformer saturation under a certain condition, seriously impacting the secure operation of power system. Some distribution networks used 4TV method to restrain ferroresonance and achieved good effects. However, this method performed ineffective in other distribution networks. To solve this problem, the simulation model was established based on ATP-EMTP program. This paper made comprehensive research on the advantages and disadvantages of 4TV method and drew a comparison between connecting ways of 4TV method. It is proved out for electric power department to apply the results from above-mentioned research in practice to improve the power supply reliability of power distribution system.
机译:分配网络由于电磁电压变压器饱和度在一定条件下引起的铁铿,严重影响电力系统的安全运行,分配网络可能会出现长时间过电压。一些分销网络使用4TV方法来抑制成分术并取得了良好的效果。然而,该方法在其他分发网络中执行无效。为了解决这个问题,基于ATP-EMTP程序建立了仿真模型。本文对4TV方法的优缺点进行了综合研究,并在4TV方法的连接方式之间进行了比较。事实证明,电力部门在实践中应用了上述研究的结果,以提高配电系统的供电可靠性。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号