首页> 外文会议>International Conference on Performance-based Fire and Fire Protection Engineering >Small Scale Experiment Study on the Fireproof Distance of Oil Tank Fires
【24h】

Small Scale Experiment Study on the Fireproof Distance of Oil Tank Fires

机译:油箱火灾防火距离的小规模实验研究

获取原文

摘要

Groups of small scale experiments were carried out by two stainless steel circular pans with 205mm diameter to simulate oil tank fire scenarios. The main burning pan was filled with 200ml No.O diesel with 100ml water below acting as the fire source which was ignited by 5ml oil. Another pan was filled with 100ml diesel and acted as the pan waiting to be ignited by the main burning pan. Changing the space between the two oil pans and the wind velocity in the experiment room, temperature and heat radiation flux of different fire conditions were recorded. Representing the diameter of the main burning pan as D, the results show that, the fireproof distance between the two diesel pans is 0.6D when wind velocity is 0.2m/s; the fireproof distance increases to 0.8D when the wind velocity is raised to 0.5m/s; When the wind velocity is lm/s, the fireproof distance changes to D. From the observation and analysis on the critical temperature and heat radiant flux received by the fuel surface of the pan waiting to be ignited, it can be seen that the radiation thermal value accumulated to about 47187.5J/m2 at the moment when the oil pan is ignited.
机译:小规模实验组由两种不锈钢圆盘连杆进行,直径为205mm,模拟油箱火情况。主要的燃烧盘用200ml No.O柴油填充,下面用100ml水作为火源,用5ml油点燃。另一个平底锅装满了100ml柴油,并充当了锅,等待由主燃锅点燃。记录了试验室内两种油锅和风速之间的空间,记录了不同火灾条件的温度和热辐射通量。表示主燃烧盘的直径为D,结果表明,当风速为0.2m / s时,两个柴油机之间的防火距离为0.6d;当风速升高到0.5m / s时,防火距离增加到0.8d;当风速为LM / s时,防火距离变为D.从观察和分析通过锅内燃料表面接收的临界温度和散热通量等待被点燃,可以看出辐射热当油底壳点燃时,值累积至约47187.5J / m2。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号