首页> 外文会议>International Conference on Future Electrical Power and Energy Systems >Scheme Design and Analysis of Variable Condition of Evaporative Condenser for Steam Condensing of Steam Feeding Water Pump for 1000MW Air-cooled Unit
【24h】

Scheme Design and Analysis of Variable Condition of Evaporative Condenser for Steam Condensing of Steam Feeding Water Pump for 1000MW Air-cooled Unit

机译:蒸汽冷凝蒸汽冷凝蒸汽冷凝器变速条件的方案设计与分析1000MW风冷单元

获取原文

摘要

Evaporative condenser for steam condensing of mini-turbine of steam feeding water pump for 1000 MW air-cooled unit is designed. Variable working condition is analyzed based on the reverse flow between steam and air. The results show that the condensing temperature of the steam in the tube increases with the air temperature and water film temperature increasing. The condensing temperature of the steam decreases with the water flow rate increasing and the wind velocity increasing. The evaporation capacity of the water outside the tube increases with wind velocity increasing. This paper can be refered when evaporation condenser is applied in thermal power plant.
机译:设计了用于1000 MW风冷单元的蒸汽送水泵蒸汽送水泵蒸汽冷凝器的蒸发冷凝器。基于蒸汽和空气之间的反向流分析可变工作条件。结果表明,管中蒸汽的冷凝温度随空气温度和水膜温度的增加而增加。蒸汽的冷凝温度随着水流速的增加而减小,而风速增加。管外部的蒸发能力随风速增加而增加。当蒸发冷凝器应用在火电厂时,可以参考本文。