首页> 外文会议>International Conference on Alternative Energy in Developing Countries and Emerging Economies >FRT Capability in DFIG based Wind Turbines using DVR with Combined Feed-Forward and Feed-Back Control
【24h】

FRT Capability in DFIG based Wind Turbines using DVR with Combined Feed-Forward and Feed-Back Control

机译:使用DVR的基于DFIG的风力涡轮机的FRT能力,具有组合前馈和反馈控制

获取原文

摘要

In this paper, Dynamic Voltage Restorer (DVR) based series compensation of the voltage to provide Fault Ride Through (FRT) and reactive power support is discussed. The control of DVR is crucial in order to improve the FRT capability in Doubly Fed Induction Generator (DFIG) based wind turbines. This is observed in terms of voltage sag mitigation capability, active and reactive power support without tripping and fault current control. To achieve a flexible control solution for balanced and unbalanced fault conditions, a combination of Feed-forward and Feedback control is discussed in this paper. The advantage of utilizing this combined control is verified through MATLAB/Simulink based simulation results of a 1.5 MW grid connected DFIG based wind turbine. The results show good transient and steady-state response and good reactive power support during various fault scenarios. The results are verified for the recent updated grid code standards.
机译:本文讨论了基于动态电压恢复器(DVR)的电压级别补偿,以提供故障乘坐(FRT)和无功功率支持。 DVR的控制是至关重要的,以便提高基于双馈电气涡轮机(DFIG)的风力涡轮机的FRT能力。在没有跳闸和故障电流控制的情况下,在电压下滑缓解能力,主动和无功功率支撑件方面观察到这一点。为了实现平衡和不平衡故障条件的灵活控制解决方案,本文讨论了前馈和反馈控制的组合。利用该组合控制的优点通过基于Matlab / Simulink基于基于1.5MW网格连接的DFig的风力涡轮机的模拟结果来验证。结果在各种故障方案期间显示出良好的瞬态和稳态响应和良好的无功功率支持。结果验证了最近更新的网格代码标准。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号