FIELD MEASUREMENTS AND PERFORMANCE EVALUATION OF CO_2 SUPERMARKET REFRIGERATION SYSTEMS

机译:Co_2超市制冷系统的现场测量和性能评估

获取原文

摘要

This paper studies field measurements and performance analysis of eight supermarkets in Sweden among which five supermarkets use CO_2 and three use HFC as the refrigerant. The differences in system design are discussed and detailed performance evaluation of one of the systems is presented. The performances of all the supermarkets are compared and the reasons for higher or lower energy efficiency are discussed. Some key components of CO_2 systems are evaluated, as well. According to the results, the older CO_2 systems have lower COP than the reference systems. High vapour fraction in low temperature cabinets inlet, relatively high amount of internal and external superheating and 10-15% lower overall efficiency of low temperature compressors compared to the other systems are some of the main reasons for this lower COP. But, the newer CO_2 systems proved to have higher efficiency, or at least, as energy-efficient as the conventional systems. This originates from the modification in the system design and more efficient components. System design modification includes two-stage expansion by receiver and flash gas by-pass. The newer CO_2 components have higher efficiency; medium temperature level compressors have 5-10% higher overall efficiency compared to HFC and older CO_2 compressors and the cabinets run with lower superheating so the system can be controlled to run at higher evaporation temperatures. This study shows that CO_2 systems have comparable COP to advanced conventional systems applied in Sweden.
机译:本文研究瑞典八个超市的现场测量和性能分析,其中五个超市使用CO_2和三次使用HFC作为制冷剂。讨论了系统设计的差异,并提出了一个系统的详细性能评估。比较所有超市的性能,讨论了更高或更低的能量效率的原因。还评估了CO_2系统的一些关键组件。根据结果​​,较旧的CO_2系统具有比参考系统更低的COP。低温柜内的高蒸气分数,相对较高的内部和外部过热量和10-15%的低温压缩机总体效率降低了与其他系统相比是这一较低警察的主要原因。但是,较新的CO_2系统证明具有更高的效率,或者至少是作为传统系统的节能。这源自系统设计中的修改和更高效的组件。系统设计修改包括接收器和闪光气体旁路的两级扩展。较新的CO_2组件具有更高的效率;与HFC和较旧的CO_2压缩机相比,中温水平压缩机具有5-10%的整体效率,并且机柜通过较低的过热运行,因此可以控制系统以在更高的蒸发温度下运行。本研究表明,CO_2系统对瑞典应用的高级传统系统具有可比的COP。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号