The high electric power consumption of air conditioning in communication base station needs to be solved urgently. This paper presents a new technology to discharge excess heat from a communication plant by utilizing the heat exchanger when the outdoor temperature is low enough. Then it compares the applied effects between two types of heat exchanger in a typical base station located in Beijing of China. It is found that this technology is feasible in Beijing of China. The plate heat exchanger can cool the station instead of air conditioning for about 5014 hours each year, and the corresponding electronic power saving rate reaches up to 29%. The plate heat exchanger applied effects are superior to the heat pipe heat exchanger.
机译:需要紧急解决通信基站中空调的高电力消耗。本文提出了一种新技术,通过在户外温度足够低时,通过利用热交换器从通信设备中排出过量的热量。然后它比较了位于中国北京的典型基站两种类型的热交换器之间的应用效果。结果发现,该技术在中国北京是可行的。板式换热器可以冷却站而不是空调每年约5014小时,相应的电子省电率达到高达29%。板式换热器施加的效果优于热管热交换器。