A twisted tape is inserted into a double pipe u-tube heat exchanger with a view to generate swirl flow, thereby enhancing the heat transfer rate of the fluids flowing in it. Experimental investigations of heat transfer enhancement and variation of friction factor have been presented for a typical test section of a u-tube double pipe heat exchanger involving a circular tube filled with a full length insert. The flow is under forced convection with Reynolds Number varying from 3,000 to 31,000. From the experimental data, heat transfer coefficient, friction factor, and thermal performance with the twisted tape inserts were calculated and compared with the plain tube data. The results show that there were a significant increase in heat transfer coefficient, friction factor, and it was found that the thermal Performance of smooth tube is better than the full length twisted tape by 2.0-2.2 times.
机译:用扭曲的带插入双管U形管热交换器中,以产生旋流,从而提高流动的流体的传热速率。已经介绍了涉及填充有全长插入件的圆管的U形管双管热交换器的典型试验部分的传热增强和摩擦因子变化的实验研究。该流量受到强制对流,雷诺数从3,000到31,000之间变化。从实验数据,传热系数,摩擦系数和与双绞带插入件的热性能进行了计算,并与普通管数据进行比较。结果表明,传热系数,摩擦系数显着增加,发现光滑管的热性能优于全长捻胶带2.0-2.2倍。