Fault Location in MV Unearthed Distribution Network Using the Undamped Frequency of the Transient Signal

机译:使用瞬态信号的未扫描频率的MV发出分配网络中的故障位置

获取原文

摘要

This paper present a method to locate a fault location for single phase to earth fault in medium voltage (MV) unearthed network using undamped frequency of the transient signal. During the earth fault, a transient component in the fault signal provides valuable information for fault location purposes. The fault distance is formulated using the lumped parameter model. In this paper, the properties of Hilbert transformation are used to estimate the damping attenuation of transient signal. The networks considered are assumed to be radially operated and modelled using ATPDraw program. Furthermore, the accuracy of technique was tested on parameters such as a fault distance, fault resistance and the voltage inception angle. Some sources of error affecting the method accuracy, are explained. Finally, the possible correction technique is explained to compensate the computation error.
机译:本文在使用瞬态信号的未扫描频率的瞬态信号的频率下,本文提出了一种用于在中电压(MV)出土网络中的单相故障的故障位置。在接地故障期间,故障信号中的瞬态分量为故障定位目的提供有价值的信息。使用大块参数模型配制故障距离。本文使用Hilbert转化的性质用于估计瞬态信号的阻尼衰减。假设所考虑的网络是使用ATPDraw程序进行径向操作和建模的。此外,在故障距离,故障电阻和电压截止角的参数上测试了技术的精度。解释了一些影响方法精度的误差来源。最后,解释了可能的校正技术以补偿计算误差。