首页> 外文会议>International Conference on Industry, Information System and Material Engineering >Cold and heat source energy-saving reconstruction for central air-conditioning system in a research and development center of Shanghai
【24h】

Cold and heat source energy-saving reconstruction for central air-conditioning system in a research and development center of Shanghai

机译:上海研发中心中央空调系统的冷热源节能重建

获取原文

摘要

Central air-conditioning energy consumption accounts for a large proportion of the buildings. And cold and heat source energy consumption accounts for about two-thirds of central air-conditioning system. For a research and development center in Shanghai, because cold and heat source capacity largely surpasses the actual demand, we propose to combine with cold sources of the two buildings. We call it "two-in-one" reconstruction. When cooling load is small, we use cold source in one building to support the two buildings. After implementation, by return on investment analysis, the average electric energy-saving rate is 9.6%. Investment can be recovered within one year.
机译:中央空调能耗占大部分建筑物。冷热源能耗占中央空调系统的三分之二。对于上海的研发中心,因为冷热源容量在很大程度上超过了实际需求,我们建议将两个建筑物的冷源相结合。我们称之为“双向”重建。当冷却负荷很小时,我们在一个建筑物中使用冷源来支持两座建筑物。实施后,通过投资回报分析,平均电节能率为9.6%。可以在一年内恢复投资。