Manitoba Hydro experienced two flashovers of "clean" FRP hot-sticks during cold weather 550 kV ac live-line work under steady-state system conditions. Subsequent laboratory testing demonstrated the reduced voltage withstand capability of the hot-stick resulting from extremely light levels (~2-3 μg/cm~2) of Equivalent Salt Deposit Density (ESDD) contamination, particularly under freezing conditions. Hot-stick hygiene protocols have been created to address threshold contamination levels. Further cold weather testing is planned to address Manitoba Hydro's full spectrum of field work to -22°C.
机译:Manitoba Hydro经历了寒冷天气550 kV交流电源线在稳态系统条件下的“清洁”FRP热棒的两个闪光灯。随后的实验室测试表明,热棒的电压耐受能力降低,导致的热粘度(〜2-3μg/ cm〜2)等同盐沉积密度(ESDD)污染,特别是在冷冻条件下。采用热粘卫生协议来解决阈值污染水平。计划进一步寒冷的天气检测来解决Manitoba Hydro的全谱田间为-22°C。