首页> 外文会议>International Conference on Civil Engineering and Transportation >Finite Element Analysis on Mechanic Behavior of Joints between Elevated Columns and Truss Columns in Substation Frame
【24h】

Finite Element Analysis on Mechanic Behavior of Joints between Elevated Columns and Truss Columns in Substation Frame

机译:变电站架升高柱和桁架柱关节力学行为的有限元分析

获取原文

摘要

Finite element analysis have been carried out in order to study the mechanical properties of the joints between elevated columns and truss column in substation frame. Firstly, the numerical results and the experimental ones were compared to verify the efficiency of the FEM model. Then, the whole process of elastic-plastic analysis was carried out to the prototype structure. The results show that when the bottom of the elevated column was yielding, the stress of the stiffeners at the joint is small, which can meet the design principle of "strong joint - weak member" criterion. Furthermore, when the structure enters into the elastic-plastic stage, the stress in the upper stiffeners at the horizontal load direction is large and most of them yield, but the stress in the plane gusset plate of the joint is still small.
机译:已经进行了有限元分析,以研究变电器框架中升高的柱和桁架柱之间的接头的机械性能。首先,比较数值结果和实验组,以验证有限元模型的效率。然后,对原型结构进行了弹性塑性分析的整个过程。结果表明,当升高的柱的底部产生时,接头处的加强筋的应力小,这可以满足“强关节弱成员”标准的设计原理。此外,当结构进入弹性塑料阶段时,水平载荷方向上的上加强件中的应力大,并且它们中的大部分产生,但是接头的平面角撑板中的应力仍然很小。