【24h】

Corrosion management for data centers

机译:数据中心的腐蚀管理

获取原文

摘要

The recent interest in air-side cooling and the spread of data centers into geographies with higher levels of atmospheric contamination is requiring more attention towards air quality management in data centers. One concern of air side economization is an increase in contamination levels potentially leading to more failures and outages of the IT equipment. In this paper we describe a corrosion measurement and management technology that enables high accuracy and real time monitoring of the gaseous contamination. The synergistic effects of indoor air temperature and relative humidity on corrosion rates are investigated and the spatial and the temporal variations of the corrosivity are established. Filtering of the outside air, both for particulate and gaseous contamination can mitigate air contamination in data centers. Implementing a facility wide air quality monitoring system promises the safe use of air-side economizers and would establish appropriate filtering, which enable early prevention of critical situations for information technology (IT) equipment operations.
机译:近期对空心冷却的兴趣和数据中心的扩散进入具有更高水平的大气污染的地理位置,需要更多地关注数据中心的空气质量管理。空中侧的一个问题是污染水平的增加,可能导致更多的失败和IT设备的中断。在本文中,我们描述了一种腐蚀测量和管理技术,可实现高精度和对气体污染的实时监测。研究室内空气温度和相对湿度对腐蚀速率的协同效应,并建立了腐蚀性的空间和时间变化。用于颗粒状和气态污染的外部空气过滤可以减轻数据中心的空气污染。实施设施宽空气质量监测系统承诺安全使用空气侧经济体,并建立适当的过滤,这使得早期预防信息技术(IT)设备运营的关键情况。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号