Use of plate thermometers for better estimate of fire development

机译:使用板温度计的使用以更好地估计火灾开发

获取原文

摘要

The concept of Adiabatic Surface Temperature (AST) opens possibilities to calculate heat transfer to a solid surface based on one temperature instead of two as is needed when heat transfer by both radiation and convection must be considered. The Adiabatic Surface Temperature is defined as the temperature of a surface which cannot absorb or lose heat to the environment, i.e. a perfect insulator. Accordingly, the AST is a weighted mean temperature of the radiation temperature and the gas temperature depending on the heat transfer coefficients. A determining factor for introducing the concept of AST is that it can be measured with a cheap and robust method called the plate thermometer (PT), even under harsh fire conditions. Alternative methods for measuring thermal exposure under similar conditions involve water cooled heat flux meters that are in most realistic situations difficult to use and very costly and impractical. This paper presents examples concerning how the concept of AST can be used in practice both in reaction-to-fire tests and in large scale scenarios where structures are exposed to high and inhomogeneous temperature conditions.
机译:绝热表面温度(AST)的概念将根据必须考虑通过辐射和对流的热传递和对流的热传递时,将热传递到固体表面计算热传递到固体表面的可能性。绝热表面温度定义为不能吸收或失去环境的表面的温度,即完美的绝缘体。因此,AST是辐射温度和气体温度的加权平均温度,这取决于传热系数。用于引入AST概念的确定因素是它可以用廉价且鲁棒的方法来测量,即使在苛刻的火灾条件下也可以用廉价且鲁棒的方法进行测量。用于在类似条件下测量热曝光的替代方法涉及水冷热通量仪表,这些热量仪表在难以使用的最逼真的情况下且非常昂贵和不切实际。本文提出了关于AST的概念如何在实践中使用的例子,无论是在反应到火灾测试中,都在结构暴露于高和不均匀的温度条件的大规模场景中。