首页> 外文会议>International Conference on Mechanical and Electrical Technology >Biocide Screening of Secondary Effluent of Sewage Treatment Plant directly reused in Power Plant Circulating Cooling Water System and the study on its properties
【24h】

Biocide Screening of Secondary Effluent of Sewage Treatment Plant directly reused in Power Plant Circulating Cooling Water System and the study on its properties

机译:污水处理厂二次污水杀菌筛选直接在发电厂循环冷却水系统中重复使用及其性能研究

获取原文

摘要

In this paper, three biocides with different mechanism were chosen to carry static test on screening from single formulation to complex formulation and bactericidal properties. The results showed that the most bactericidal biocide was isothiazolone, and the last was steady chlorine dioxide. The optimum concentration of three biocides in single formulation were isothiazolone10 mg/L, quaternary amine salt 20 mg/L and steady chlorine dioxide 20 mg/L separately. As the best complex formulation, P with optimum concentration of isothiazolone5 mg/L and steady chlorine dioxide10 mg/L, was verified as harmless for environment and also effective inhibition growth of microorganism by dynamic test.
机译:本文选择了三种具有不同机制的杀生物剂,以在单一配方中筛选静态试验,从单一配方中筛选到复合配方和杀菌性质。结果表明,最杀菌的杀生物剂是异噻唑酮,最后是二氧化碳稳定的氯。单一制剂中三种杀生物剂的最佳浓度是异噻唑酮10mg / L,季胺盐20mg / L和二氧化氯20mg / L.作为最佳复合配方,具有Isothiazolone5mg / L和二氧化氯10mg / L稳定的P的P验证了对环境无害的,并且通过动态试验也有效抑制微生物的生长。