首页> 外文会议>International Conference on Energy and Environment Technology >The experimental research and analysis of the reverse osmosis technology on the waste water reusing of the plant cooling water
【24h】

The experimental research and analysis of the reverse osmosis technology on the waste water reusing of the plant cooling water

机译:反渗透技术对植物冷却水的废水再滴水的实验研究与分析

获取原文

摘要

This paper studied the influence of the feed water PH value on the reverse osmosis system in the process of the sewage reusing of the power plant circulating water. The utmost recovery rate was made out through experiments, at different feed water PH value, on condition that the concentrated water did not scale. The influence of the PH value on the salt desalting rate of the reverse osmosis system was investigated, the results show that the highest desalination rate is up to 99.6%, when the PH value is 8.0~9.0. Comparing the different operating cost in different operating conditions, it's found that when the PH value is 8.0, the reverse osmosis systematic recovery rate is 72%, which is the most economical operating condition.
机译:本文研究了电厂循环水污水再渗透过程中饲料水pH值对反渗透系统的影响。通过实验,在不同的饲料水pH值下进行最大的恢复速率,条件是浓缩水不规模的条件。研究了pH值对反渗透体系盐脱盐率的影响,结果表明,当pH值为8.0〜9.0时,最高脱盐率高达99.6%。比较不同的操作成本在不同的操作条件下,发现当pH值为8.0时,反渗透系统恢复率为72%,这是最经济的操作条件。