首页> 外文会议>Energy and Environment Technology, 2009. ICEET '09 >The Experimental Research and Analysis of the Reverse Osmosis Technology on the Waste Water Reusing of the Plant Cooling Water
【24h】

The Experimental Research and Analysis of the Reverse Osmosis Technology on the Waste Water Reusing of the Plant Cooling Water

机译:反渗透技术对工厂冷却水废水回用的实验研究与分析

获取原文

摘要

This paper studied the influence of the feed water PH value on the reverse osmosis system in the process of the sewage reusing of the power plant circulating water. The utmost recovery rate was made out through experiments, at different feed water PH value, on condition that the concentrated water did not scale. The influence of the PH value on the salt desalting rate of the reverse osmosis system was investigated, the results show that the highest desalination rate is up to 99.6%, when the PH value is 8.0~9.0. Comparing the different operating cost in different operating conditions, itȁ9;s found that when the PH value is 8.0, the reverse osmosis systematic recovery rate is 72%, which is the most economical operating condition.
机译:本文研究了电厂循环水污水回用过程中给水PH值对反渗透系统的影响。在浓缩水不结垢的条件下,通过实验在不同的给水PH值下获得了最大的回收率。研究了PH值对反渗透系统盐分脱盐率的影响,结果表明,当PH值在8.0〜9.0时,最高脱盐率可达99.6%。比较不同工况下的不同运行成本,发现ȁ9;当PH值为8.0时,反渗透系统回收率为72%,这是最经济的工况。