首页> 外文会议>IEEE Bucharest PowerTech >Determination of the saturated inductance of transformers by analytical formulae, comparison with an electromagnetic field calculation approach and validation by on-site tests
【24h】

Determination of the saturated inductance of transformers by analytical formulae, comparison with an electromagnetic field calculation approach and validation by on-site tests

机译:通过分析公式测定变压器的饱和电感,与现场测试的电磁场计算方法比较和验证

获取原文

摘要

This document describes the determination of the saturated inductance of a transformer, which is the slope of the saturation curve Φ(I) under highly saturated conditions. This parameter, which has a strong impact on the overvoltages when energizing a transformer, has been determined from analytic formulae for a shell-type transformer. Comparisons with the values derived from an electromagnetic 3D calculation and on-site tests are also given in this paper.
机译:本文档描述了变压器的饱和电感的确定,其是高饱和条件下饱和曲线φ(i)的斜率。该参数在激励变压器时对过电压产生强烈影响,已经从壳牌型变压器的分析公式确定。本文还给出了与电磁三维计算和现场测试的价值的比较。

著录项