【24h】

OIL INFLUENCE ON THE OPTIMAL CHARGE AND PERFORMANCE OF A PROPANE CHILLER

机译:对丙烷冷却器的最佳充电和性能的影响

获取原文

摘要

The paper presents the experimental results of a charge optimization study of a water-to-water chiller of approximately 14 kW cooling capacity which uses propane as refrigerant. The unit employs a Copeland scroll compressor and two BPHE exchangers. The unit does not incorporate any liquid receiver so that the refrigerant charge strongly affects the unit performance. A complete charge optimization study was performed for two different oils: mineral ISOVG68 and POE ISOVG22. The study covered a wide range of variation of condensation temperatures, all around the typical operating conditions of this kind of equipment for AC applications. The main conclusions are that the optimal charge is strongly different, depending on the solubility of the refrigerant into the oil, and that the POE oil seems to lead to better unit performance. The performance is also plotted vs. the subcooling as to show that this is the real parameter leading to the optimum COP. The obtained volumetric and compressor efficiencies are then presented and discuss to explain the observed difference in performance.
机译:本文介绍了大约14千瓦冷却能力的水冷却器的电荷优化研究的实验结果,其使用丙烷作为制冷剂。该装置采用COPELAND滚动压缩机和两个BPHE交换机。该装置不掺入任何液体接收器,使得制冷剂电荷强烈影响单位性能。对两种不同的油来进行完整的充电优化研究:矿物Isovg68和PoE Isovg22。该研究涵盖了诸如AC应用的这种设备的典型操作条件,涵盖了很多凝结温度的变化。主要结论是,取决于制冷剂进入油的溶解度,最佳充电具有强烈不同,并且PoE油似乎导致更好的单位性能。该性能也绘制了VS.Oupcooling,以表明这是导致最佳COP的真实参数。然后呈现获得的体积和压缩机效率并讨论以解释观察到的性能差异。