首页> 外文会议>1st IIR workshop on refrigerant charge reduction in refrigerating systems (RCR 2009) >OIL INFLUENCE ON THE OPTIMAL CHARGE AND PERFORMANCE OF A PROPANE CHILLER
【24h】

OIL INFLUENCE ON THE OPTIMAL CHARGE AND PERFORMANCE OF A PROPANE CHILLER

机译:油对丙烷冷却器最佳装料和性能的影响

获取原文
获取原文并翻译 | 示例

摘要

The paper presents the experimental results of a charge optimization study of a water-to-water chiller of approximately 14 kW cooling capacity which uses propane as refrigerant. The unit employs a Copeland scroll compressor and two BPHE exchangers. The unit does not incorporate any liquid receiver so that the refrigerant charge strongly affects the unit performance. A complete charge optimization study was performed for two different oils: mineral ISOVG68 and POE ISOVG22. The study covered a wide range of variation of condensation temperatures, all around the typical operating conditions of this kind of equipment for AC applications. The main conclusions are that the optimal charge is strongly different, depending on the solubility of the refrigerant into the oil, and that the POE oil seems to lead to better unit performance. The performance is also plotted vs. the subcooling as to show that this is the real parameter leading to the optimum COP. The obtained volumetric and compressor efficiencies are then presented and discuss to explain the observed difference in performance.
机译:本文介绍了使用丙烷作为制冷剂的冷却能力约为14 kW的水对水冷却器的装料优化研究的实验结果。该机组采用了谷轮涡旋压缩机和两个BPHE交换器。该设备未安装任何液体接收器,因此制冷剂充注会严重影响设备性能。对两种不同的油进行了完整的电荷优化研究:矿物ISOVG68和POE ISOVG22。这项研究涵盖了冷凝温度的各种变化,围绕这种AC应用设备的典型运行条件进行了研究。主要结论是,取决于制冷剂在机油中的溶解度,最佳充气量存在很大差异,并且POE油似乎可以带来更好的单元性能。还绘制了性能与过冷的关系曲线,以表明这是导致最佳COP的真实参数。然后介绍获得的容积效率和压缩机效率,并进行讨论以解释观察到的性能差异。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号