首页> 外文会议>International Conference on Cryogenics Refrigeration >Experimental Study on Capacity Modulation by Variable Composition of Refrigerant Mixtur
【24h】

Experimental Study on Capacity Modulation by Variable Composition of Refrigerant Mixtur

机译:制冷剂混合物可变组成能力调节的实验研究

获取原文

摘要

A new capacity-controlled heat pump system was developed in this paper. An experimental study on capacity control of a heat pump system by variable composition has been performed using refrigerant mixture of R32/R134a. The experimental setup was made up of a refrigeration part and composition varying part. The composition varying part with a rectifier and a reservoir was connected to the junction between the condenser outlet and compressor outlet and to the throttle valve inlet. Part of the refrigerant mixture from the compressor and the condenser goes into the rectifier, as a heat source so that the heat energy to the rectifier supplied generally by external sources can be saved. When the modulation occurs, the reservoir was used to store the high volatile component of the refrigerant mixture separated from the rectifier, the low volatile component together with lubricant flows back to the main cycle. Heating capacity and coefficient of performance (COP) of the system were measured under the given conditions. The results show that about 28% of composition change was obtained. And the capacity of the system was improved by 33% as the composition of R32 increased.
机译:本文开发了一种新的容量控制热泵系统。使用R32 / R134a的制冷剂混合物进行了可变组合物通过可变组合物对热泵系统容量控制的实验研究。实验设置由制冷部分和组合物变化部分组成。具有整流器和储存器的组合物改变部分连接到冷凝器出口和压缩机出口之间的连接和节流阀入口。来自压缩机的一部分制冷剂混合物和冷凝器进入整流器,作为热源,使得可以节省通常由外部源提供的整流器的热能。当发生调制时,储存器用于将从整流器分离的制冷剂混合物的高挥发性组分存储在,低挥发性组分与润滑剂流回到主循环。在给定的条件下测量系统的加热容量和性能系数(COP)。结果表明,获得了约28%的组成变化。随着R32的组成增加,系统的容量提高了33%。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号