首页> 外文会议>Cooling Technology Institute Annual conference >Optimal Control of Admiralty Corrosion and Microbiological Growth Utilizing Multiple Halogen Sources
【24h】

Optimal Control of Admiralty Corrosion and Microbiological Growth Utilizing Multiple Halogen Sources

机译:利用多种卤素源的通道腐蚀和微生物生长的最佳控制

获取原文

摘要

Effective copper alloy and steel corrosion control, along with effective fouling control, can be major challenges in industrial cooling water systems. Major issues include achieving effective chlorine and copper alloy inhibitor feed rates and proper residual control. This paper provides a case history that describes how monitoring of cooling water chemistry, corrosion monitoring, and fouling monitoring were used to achieve effective performance results under difficult conditions. Advantages of using activated bromide to supplement the gaseous chlorine application are discussed. Some of the monitoring tools used to determine adequate treatment concentrations and to optimize performance with respect to chemical costs and avoided costs are described.
机译:有效的铜合金和钢腐蚀控制,以及有效的污垢控制,可能是工业冷却水系统中的主要挑战。主要问题包括实现有效的氯和铜合金抑制剂饲料速率和适当的残留控制。本文提供了一种案例历史,描述了如何监控冷却水化学,腐蚀监测和污垢监测,用于在困难的条件下实现有效的性能结果。讨论了使用活性溴化物补充气态氯应用的优点。描述了用于确定适当治疗浓度的监控工具和优化相对于化学成本和避免成本的性能。