Following it’s completion in 2008, Greater Vancouver’s Seymour-Capilano Filtration Plant will contain the world’s largest operational UV facility for the disinfection of drinking water. Validation testing was used to create a model for the calculation of the reduction equivalent dose, having a validation envelope that fully encompassed the expected operational range of flow and water quality as well as the associated UV system operational parameters needed to maintain the required dose. Additional validation data was collected for the development of prediction models for UV intensity, power consumption and headloss for use in the UV systems control strategy and demonstration of compliance with performance guarantees. In addition to the off-site validation of the UV system, on-site performance testing is also to be conducted following installation of the UV equipment. On-site performance testing will include confirmation of performance guarantees including head loss, power consumption and biodosimetry based dose delivery evaluation. On-site biodosimetry testing is host to several challenges that are unique to a water treatment facility as compared to a test facility that has specifically been designed for the sole purpose of UV unit validation. Such challenges at the Seymour-Capilano Filtration plant included the dechlorination of the source water, determination of injection points for the challenge organism and UV absorber, confirmation of adequate mixing prior to influent and effluent sampling ports, management and discharge of the UV unit effluent.
机译:遵循它在2008年完成后,更大的温哥华的Seymour-Capilano过滤厂将包含世界上最大的运营紫外线设施,用于消毒饮用水。验证测试用于创建用于计算减少等效剂量的模型,该验证信封完全包含了预期的流量和水质范围以及维护所需剂量所需的相关的UV系统操作参数。收集了用于开发UV强度,功耗和头阵列的预测模型的额外验证数据,以便在UV系统控制策略中使用,并遵守性能保证。除了UV系统的非现场验证之外,在安装UV设备之外还将进行现场性能测试。现场的性能测试将包括确认性能保证,包括头部损耗,功耗和基于生物渗透压剂的剂量递送评估。与测试设施相比,现场Biodosimetry测试是多个挑战,这些挑战是水处理设施的独特,该挑战是专门用于UV单元验证的唯一目的的测试设施。 Seymour-CapiLano过滤装置的这种挑战包括源水的脱氯,挑战生物和紫外线吸收的注射点测定,在流出物和流出物采样端口,管理和排放的紫外线单元流出物之前确认足够混合。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号