首页> 外文学位 >Impacts of process upsets and transient water quality events on UV disinfection performance at Ontario water treatment facilities.
【24h】

Impacts of process upsets and transient water quality events on UV disinfection performance at Ontario water treatment facilities.

机译:安大略省水处理设施的工艺异常和瞬态水质事件对紫外线消毒性能的影响。

获取原文
获取原文并翻译 | 示例

摘要

The effectiveness of UV disinfection at two Ontario drinking water facilities during sub-optimum water quality conditions was studied. The disinfection performance of a pilot-scale low pressure UV reactor, delivering a reduction equivalent dose of 60--90 mJ/cm2, was not negatively impacted by either pre- and post-filter water quality conditions experienced at the two treatment facilities. Enmeshment of coliforms within particles, resulting in reduced inactivation levels did occur in samples of raw water from one facility that were coagulated with alum and alum+polymer at turbidities >6 NTU and exposed to low UV dosages (≤10 mJ/cm2). No evidence of coliform enmeshment was observed in tests that examined raw water coagulation with STERNPACRTM/activated silica/sand/LT27A. No conclusive evidence was observed that would relate changes in inactivation efficiency as a result of bacterial enmeshment to turbidity or particle count data.
机译:研究了在亚最佳水质条件下在安大略省的两个饮用水设施中进行紫外线消毒的效果。中试规模的低压紫外线反应器的消毒性能(当量还原剂量为60--90 mJ / cm2)不受两个处理设施的过滤前和过滤后水质条件的不利影响。大肠菌群在颗粒内的啮合,导致灭活水平降低,来自一家工厂的原水样品确实发生了沉淀,这些样品用明矾和明矾+聚合物以> 6 NTU的浊度凝结并暴露于低紫外线剂量(≤10mJ / cm2)。在用STERNPACRTM /活性硅胶/砂/ LT27A检查原水凝结的测试中,没有观察到大肠菌被网状化的迹象。没有观察到确凿的证据表明细菌啮合导致灭活效率的变化与浊度或颗粒计数数据有关。

著录项

  • 作者

    Quinn, Claire.;

  • 作者单位

    University of Toronto (Canada).;

  • 授予单位 University of Toronto (Canada).;
  • 学科 Engineering Civil.; Engineering Sanitary and Municipal.
  • 学位 M.A.Sc.
  • 年度 2004
  • 页码 155 p.
  • 总页数 155
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类 建筑科学;建筑科学;
  • 关键词

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文