首页> 外文会议>International Electronics Packaging Technical Conference and Exhibition >TECHNIQUES FOR CONTROLLING AIRFLOW DISTRIBUTION IN RAISED-FLOOR DATA CENTERS
【24h】

TECHNIQUES FOR CONTROLLING AIRFLOW DISTRIBUTION IN RAISED-FLOOR DATA CENTERS

机译:控制升降地板数据中心气流分布的技术

获取原文

摘要

In raised-floor data centers, the airflow rates through the perforated tiles must meet the cooling requirements of the computer servers placed next to the tiles. The data centers house a wide range of equipment, and the heat load pattern on the floor can be quite arbitrary and changes as the data center evolves. To achieve optimum utilization of the floor space and the flexibility for rearrangement and retrofitting, the designers and managers of data centers must be able to modify the airflow rates through the perforated tiles. The airflow rates through the perforated tiles are governed primarily by the pressure distribution under the raised floor. Thus, the key to modifying the flow rates is to influence the flow field in the plenum. This paper discusses a number of techniques that can be used for controlling airflow distribution. These techniques involve changing the plenum height and open area of perforated tiles, and installing thin (solid and perforated) partitions in the plenum, A number of case studies, using a mathematical model, are presented to demonstrate the effectiveness of these techniques.
机译:在升降地板数据中心,通过穿孔瓷砖的气流速率必须满足瓷砖旁边的计算机服务器的冷却要求。数据中心容纳各种各样的设备,地板上的热负荷图案可以是非常任意的并且随着数据中心演变而变化。为了实现地板空间的最佳利用和重排和改装的灵活性,数据中心的设计者和管理人员必须能够通过穿孔瓦片来修改气流速率。穿过穿孔砖的气流速率主要受凸起地板下的压力分布的限制。因此,修改流速的关键是影响增压室中的流场。本文讨论了许多可用于控制气流分布的技术。这些技术包括改变增压室高度和穿孔瓦片的开口面积,并且在所述气室中,A号码案例研究的安装薄(固体和穿孔)分区,使用数学模型,被呈现给证明这些技术的有效性。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号