Distribution of Cooling Airflow in a Raised-Floor Data Center

机译:高架地板数据中心中的冷却气流分布

获取原文
获取原文并翻译 | 示例
       

摘要

For reliable operation of computer equipment in a data center, adequate cooling air must be supplied to the equipment. The distribution of cooling air through the perforated tiles in a raised-floor data center is governed by the fluid mechanics of the underfloor space. The pressure variation in that space is shown to be the cause of nonuniform distribution of airflow. The various factors that influence the distribution are discussed. The effect of floor height and tile open area is illustrated through the results for a simple configuration. The use of variable tile open area and other issues are also discussed. Calculated distributions of airflow rates are used to explain some of the observed behavior in data centers on the basis of fluid mechanics principles.
机译:为了使数据中心中的计算机设备可靠运行,必须向设备提供足够的冷却空气。通过高架地板数据中心中的多孔砖分配的冷却空气受地板空间的流体力学控制。该空间中的压力变化显示为气流分布不均匀的原因。讨论了影响分布的各种因素。通过简单配置的结果说明了地板高度和瓷砖开口面积的影响。还讨论了可变瓦片开放区域的使用和其他问题。根据流体力学原理,计算出的气流速率分布用于解释数据中心中观察到的某些行为。