首页> 外文会议>International Conference on Electric Utility Deregulation and Restructuring and Power Technologies >Study of EHV Power Grid Over-voltage Monitoring system based on Rogow ski coil
【24h】

Study of EHV Power Grid Over-voltage Monitoring system based on Rogow ski coil

机译:基于Rogow Ski线圈的EHV电网过压监测系统研究

获取原文

摘要

An EHV Power Grid Over-voltage Monitoring scheme was studied according to Rogow ski coil on earth line of transformer Bushing tap, simulation and test proved the feasibility of this scheme. With the analysis the transformer Bushing tap current in overvoltage event, a new current transformer which uses Mn and Zn as magnetic core was developed. The amplitude-frequency response of current transformer in 100Hz∼1.5MHz was less than or equal to 5%. Based on the simulation and experiment of bushing tap, accurate simulation model from transformer bushing tap current to voltage was established, integration reduction and trigger circuit was designed in addition. Upon the above research, the EHV Power Grid Over-voltage Monitoring System based on Rogow ski coil was developed. The System was calibrated by the Fifth Metering and Measuring Centre Station for Mechanical Industry. The amplitude and wave form parameters measurement accuracy for standard lightning and operation overvoltage were 5.0. After the commissioning, the Over-voltage Monitoring System operates satisfactorily.
机译:研究了EHV电网过电压监测方案,根据变压器衬套水龙头接地线上的Rogow Ski线圈,仿真和测试证明了该方案的可行性。通过分析过电压事件中的变压器衬套抽头电流,开发了一种使用Mn和Zn作为磁芯的新型电流互感器。 100Hz〜1.5MHz在100Hz〜1.5MHz中的电压频率响应小于或等于5%。基于套管龙头的仿真和实验,建立了从变压器衬套抽头电流的精确仿真模型,另外设计了整合和触发电路。在上述研究之上,开发了基于Rogow Ski线圈的EHV电网过电压监测系统。该系统由第五计量和测量中心校准机械工业。标准闪电和操作过电压的幅度和波形参数测量精度为5.0。调试后,过电压监控系统令人满意。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号