首页> 外文会议>2011 4th International Conference on Electric Utility Deregulation and Restructuring and Power Technologies >Study of EHV Power Grid Over-voltage Monitoring system based on Rogow ski coil
【24h】

Study of EHV Power Grid Over-voltage Monitoring system based on Rogow ski coil

机译:基于Rogow滑雪线圈的超高压电网过电压监测系统的研究

获取原文

摘要

An EHV Power Grid Over-voltage Monitoring scheme was studied according to Rogow ski coil on earth line of transformer Bushing tap, simulation and test proved the feasibility of this scheme. With the analysis the transformer Bushing tap current in overvoltage event, a new current transformer which uses Mn and Zn as magnetic core was developed. The amplitude-frequency response of current transformer in 100Hz∼1.5MHz was less than or equal to 5%. Based on the simulation and experiment of bushing tap, accurate simulation model from transformer bushing tap current to voltage was established, integration reduction and trigger circuit was designed in addition. Upon the above research, the EHV Power Grid Over-voltage Monitoring System based on Rogow ski coil was developed. The System was calibrated by the Fifth Metering and Measuring Centre Station for Mechanical Industry. The amplitude and wave form parameters measurement accuracy for standard lightning and operation overvoltage were 5.0. After the commissioning, the Over-voltage Monitoring System operates satisfactorily.
机译:根据变压器套管抽头接地线上的Rogow滑雪线圈,研究了超高压电网过电压监测方案,仿真和试验证明了该方案的可行性。通过分析变压器在过电压情况下的套管抽头电流,开发了一种以Mn和Zn为磁芯的新型电流互感器。电流互感器在100Hz〜1.5MHz的幅频响应小于或等于5%。在套管抽头仿真实验的基础上,建立了从变压器套管抽头电流到电压的精确仿真模型,并设计了积分降低和触发电路。基于以上研究,开发了基于Rogow滑雪线圈的超高压电网过电压监测系统。该系统已由机械工业第五计量和测量中心站进行了校准。标准雷电和操作过电压的幅度和波形参数测量精度为5.0。调试后,过电压监控系统运行良好。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号