Islanding tests of residential PV systems interconnected to utility distribution lines

机译:住宅光伏系统的岛屿测试与公用事业配送线相互连接

获取原文

摘要

Six residential PV systems (maximum electric power of 2.82kW/system) are interconnected to utility grids. Islanding tests of these systems were carried out in two cases that the generating power is nearly equal to the various loads (R,L,C) of the systems and not, by manually disconnecting them to the utility grids. Islanding time were 0.2~5.O seconds owing to the kinds of the loads. The islanding times of the systems were analyzed by measuring the active power flows and the reactive power flows.
机译:六个住宅PV系统(最大电力为2.82kW / System)与实用电网相互连接。这些系统的岛屿测试是在两种情况下进行的,发电功率几乎等于系统的各种负载(R,L,C),而不是通过手动断开本实用网格。由于载荷的种类,岛屿时间为0.2〜5.0秒。通过测量有源电流和无功功率流动来分析系统的岛屿时间。