Field study on natural ventilation system using natural energy in a university school building and its measured results in the 3rd year after school opening

机译:大学学校建设中自然能源自然通风系统的田间研究及其在开放后的第三年中的衡量结果

获取原文

摘要

The results of field investigation on the performance of a natural ventilation system combined with solar chimney and cool pit introduced into a university building in Kitakyushu city are described. In the third year after school opening, natural ventilation was observed during the hours of 61% of cooling period. The total amount of cooling under natural ventilation conditions was 58.9GJ at the measured block of the building with 4,392m{sup}2 of floor area. It was confirmed that heat exchange performance of cool pit was not lowered after three years' operation.
机译:描述了对天然通风系统性能的现场调查结果与太阳能烟囱和凉爽坑引入了北京市北京市大学建筑。在参加开放后的第三年,在冷却期的61%的时间内观察到自然通风。自然通风条件下的冷却总量为58.9GJ,在建筑物的测量块,占地面积4,392m {Sup} 2。证实,在三年的操作后,冷冻坑的热交换性能不会降低。