Electronic sectionalizer control methodology for improved distribution system reliability

机译:用于改进分配系统可靠性的电子分区控制方法

获取原文

摘要

A new methodology for sectionalizer control has been developed that provides more security for applications where system transient currents may cause actuate pickup. Actuate pickup, particularly on ground sensing, may occur during upline ground faults when the sudden load current imbalance is compounded by the unfaulted phase voltage rise causing magnetizing current inrush into a large amount of distribution transformers downline from the sectionalizer. Also, motor backfeed and nonsimultaneous fault clearing may cause actuate pickup if the load is sufficiently large. The control has five automatic restraint features: inrush restraint, count restraint, time-integrated threshold restraint, response restraint, and ground restraint. The last three are new features. The control logic was tested by connecting a prototype to the transient network analyzer and simulating conditions that were suspected of causing problems.
机译:已经开发了一种用于分区控制器的新方法,为系统瞬态电流可能导致启动拾取的应用提供更多安全性。致动拾取器,特别是在接地传感上,在上线接地故障期间,当通过未卸载的相位电压升高使突然负载电流不平衡升高,导致磁化电流涌入从分截面的大量分配变压器向下线。此外,如果负载足够大,电机反馈和无菌故障清除可能会导致启动拾取器。该控件具有五种自动约束功能:浪涌约束,计数约束,时间累积阈值约束,响应约束和地面约束。最后三个是新功能。通过将原型连接到瞬态网络分析仪和疑似造成问题的条件来测试控制逻辑。