首页> 外文会议>Asia-Pacific Power and Energy Engineering Conference >Research on Lightning Over-voltage Protection for 500kV GIS Substation
【24h】

Research on Lightning Over-voltage Protection for 500kV GIS Substation

机译:500kV GIS变电站雷电过电压保护研究

获取原文

摘要

This paper combines incoming lines with 500kv GIS substation, considering the influence of the impulse voltage-second characteristics of insulator strings, the impulse corona of incoming lines, the impulse grounding resistance of tower and the position of lightning. ATP-EMTP simulation program is applied to analyze the lightning over-voltage of 500kv GIS substation. The result shows that impulse corona and the resistance of tower which is close to the substation have great influence on over-voltage, when lightning strike the tower which is close to terminal door-typed structure, the lightning over-voltage may be not the most serious, and when the over-voltage of the equipment is very serious, a group of arrester is installed which can decrease the over-voltage effectively. This research thinking takes safety and economy into account, which can provide new reference for the engineering.
机译:本文将传入线与500kV GIS变电站相结合,考虑到绝缘子串的脉冲电压第二特征的影响,输入线的脉动电晕,塔的脉冲接地电阻和闪电的位置。 ATP-EMTP仿真程序应用于分析500kV GIS变电站的闪电过电压。结果表明,脉动电晕和塔的电阻接近变电站对过电压的影响很大,当雷击接近端子门式结构的塔时,雷电过电压可能不是最多的严重,并且当设备的过电压非常严重时,安装了一组避雷器,可以有效地降低过电压。这项研究思维考虑了安全性和经济,这可以为工程提供新的参考。