首页> 外文会议>International Conference on Manufacturing Science and Engineering >Research on Lightning Over-voltage and Lightning Protection of 500kV HGIS Substation
【24h】

Research on Lightning Over-voltage and Lightning Protection of 500kV HGIS Substation

机译:500kV HGIS变电站雷电过压和防雷研究

获取原文

摘要

To ensure safe and reliable operation of the substation, avoid the equipment damage caused by lightning wave invasion, which threats the safe operation of power system, it is necessary to research the influence factors of the substation lightning overvoltage and lightning protection measures. Taking a 500kV HGIS substation as the research object, a simulation model is established. Based on EMTP-ATP, this paper simulates the lightning striking the top of the tower and back-flashover occurring at the coming line of transmission line. Based on the principle of single variable, the factors which affect lightning overvoltage amplitude was studied, the change rule of amplitude was summarized. By configuring the quantity of arrester and the location of installation, through simulation, it determined that installing arresters at the line entry and GIS bus is the most reasonable lightning protection scheme.
机译:为确保变电站的安全可靠运行,避免闪电侵入引起的设备损坏,这威胁到电力系统的安全运行,有必要研究变电站雷电过电压和防雷措施的影响因素。采用500kV HGIS变电站作为研究对象,建立了仿真模型。基于EMTP-ATP,本文模拟了在传输线路上发生的塔顶的闪电和背部闪光灯。基于单变的原理,研究了影响雷电过电压幅度的因素,总结了振幅的变化规律。通过配置避雷器数量和安装的位置,通过仿真,确定在线条目和GIS总线安装避雷器是最合理的防雷方案。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号