首页> 外文会议>International Conference on Material and Manufacturing Technology >The Study of Ferromagnetic Resonance Overvoltage and its Suppression Methods in 35kv Power System
【24h】

The Study of Ferromagnetic Resonance Overvoltage and its Suppression Methods in 35kv Power System

机译:35kV电力系统铁磁共振过电压及其抑制方法研究

获取原文

摘要

Ferromagnetic resonance overvoltage is an internal overvoltage and it often occurred in the power distribution system which neutral point ungrounded. A 35kV power system is used as the prototype to establish the 35 kV substation's simulation model which is based on the ATP - EMTP and ferromagnetic resonance overvoltage is researched and analyzed In this paper. The ferromagnetic resonance overvoltage which is stimulated by single-phase ground fault is studied in this paper studied and ferromagnetic resonance suppression methods were also studied. The results show that the nonlinear resistor is connected in the PT primary neutral side and small resistance is connected in the PT open delta is effectively methods which can restrain ferromagnetic resonance overvoltage.
机译:铁磁谐振过电压是内部过电压,它通常发生在中性点未接地的配电系统中。 35kV电源系统用作建立35 kV变电站的原型,基于ATP - EMTP和铁磁谐振过电压,并在本文中进行了研究和分析。在本文研究中,研究了通过单相接地故障刺激的铁磁共振过电压。研究和铁磁共振抑制方法也研究。结果表明,非线性电阻在PT初级中性侧连接,在PT开放δ中连接小电阻是有效的方法,可以抑制铁磁谐振过电压。