Hotels are high-energy consuming buildings with numerous demands for heating and cooling at several temperature levels. The heating load is largely dominated by hot water production (28%: NVE, 2016) in order to meet the hot water consumption of the many guests. The current practice is to have several independent heating and cooling systems. Most of the hotels in northern Europe use thermally inefficient methods, such as electric boilers or district heating stations, which simultaneously provide high temperature heat for tap water and a high temperature space heating circuit. Currently, CO_2 technologies are widely used in Scandinavia at an industrial scale thanks to their high efficiency in cold climates. The first combined CO_2 heating, air conditioning and hot tap water system with an integrated thermal storage for a hotel is installed (2018) in Norway (Trondheim) and is presented in this paper. The working principal of the system is clearly described in this work and data obtained from the first test campaigns are presented. The heat pump has an installed capacity of 280 kW. If cooling is needed, chilled water for AC cooling is used as a heat source. Heat is rejected to two different circuits in the gas cooler in order to achieve high and medium temperature levels according to the setpoint of the different heating applications. The tap water system is mainly composed of a 6 m3 buffer tank storage unit, in order to ensure continuous production of hot water to covers the peak demand period. Preliminary results show significant energy savings (59-68%) and peak power reductions (15-45%).
机译:酒店是高耗能的建筑,在几个温度水平下进行加热和冷却的许多要求。加热负荷主要由热水生产主要为主导(28%:NVE,2016),以满足许多客人的热水消耗。目前的做法是具有几种独立的加热和冷却系统。北欧大部分酒店都使用热效的方法,例如电锅炉或地区加热站,其同时为自来水和高温空间加热回路提供高温热。目前,由于他们在寒冷气候的高效率,CO_2技术在斯堪的纳维亚广泛应用于斯堪的纳维亚。安装了第一批CO_2加热,空调和热自来水系统,为酒店的集成热储存安装(2018)在挪威(Trondheim),并在本文中提出。在本工作中清楚地描述了系统的工作原理,并提出了从第一次测试活动中获得的数据。热泵的装机容量为280千瓦。如果需要冷却,则使用用于AC冷却的冷却水作为热源。加热被拒绝在气体冷却器中的两个不同电路,以便根据不同加热应用的设定点来实现高中温度水平。自来水系统主要由6 M3缓冲罐存储单元组成,以确保连续生产热水以覆盖峰值需求期。初步结果显示出显着的节能(59-68%)和峰值功率降低(15-45%)。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号