首页> 外文会议>International Conference on Electrical Power Engineering and Applications >Laboratory Test of Current Transformer Operates Under Harmonic Conditions
【24h】

Laboratory Test of Current Transformer Operates Under Harmonic Conditions

机译:电流互感器的实验室测试在谐波条件下运行

获取原文

摘要

This research focused on the effect of harmonic to the performance of current transformer (CT) operates under harmonic conditions. Due to the increasing of harmonic in power system, the CT did not perform well. The CT may saturates due to the presence of voltage and current harmonics. In this project, a laboratory test was conducted to investigate and analyze the influence of harmonics to the CT performance. This CT has been test with different Total Harmonic Distortion Current (THDi) at primary side and constant primary current. The experiment result shows the secondary current CT errors will increases when THDi increases.
机译:本研究专注于谐波对电流变压器(CT)的性能的影响,在谐波条件下运行。由于电力系统中谐波的增加,CT没有表现良好。由于存在电压和电流谐波,CT可以饱和。在该项目中,进行了实验室测试,以调查和分析谐波对CT性能的影响。该CT在初级侧和恒定初级电流下具有不同的总谐波失真电流(THDI)。实验结果表明,当THDI增加时,二次电流CT误差会增加。