首页> 外文期刊>MATEC Web of Conferences >Performance of current transformer operate under harmonic condition and their effects on transformer differential protection
【24h】

Performance of current transformer operate under harmonic condition and their effects on transformer differential protection

机译:电流互感器在谐波条件下的性能及其对变压器差动保护的影响

获取原文
           

摘要

This paper focused to determine the performance of Current Transformer (CT) operates under harmonics condition and their effects on transformer differential protection. A laboratory test has been implemented to determine the error produced by both CT and power transformer when operating under harmonic condition. The test was performing with the actual condition, where the power transformer is connected to an adjusted nonlinear load, so that the test can be conducted with several levels of total harmonic distortion current (THD_(i)). The results shows, for THDi ranging from 16.70% to 40.88% the maximum errors occurred on CT at secondary power transformers is 27.21% and CT at primary power transformers is 8.12%. This error resulted in differential current flow 0.17A and relay trip without any fault. In this study it was found that the relays started to operate incorrectly on THD_(i)31.5%.
机译:本文重点确定谐波条件下电流互感器(CT)的性能及其对变压器差动保护的影响。已经进行了一项实验室测试,以确定谐波条件下运行时CT和电源变压器产生的误差。该测试是在实际条件下进行的,其中将电源变压器连接到调整后的非线性负载,以便可以在多个水平的总谐波失真电流(THD_(i))下进行测试。结果表明,对于THDi为16.70%至40.88%的情况,在次级电力变压器上CT上出现的最大误差为27.21%,而在初级电力变压器上CT上出现的最大误差为8.12%。该错误导致差动电流0.17A,继电器跳闸而没有任何故障。在这项研究中,发现继电器在THD_(i)31.5%上开始不正确地工作。