首页> 外文会议>International Conference on Engineering Materials, Geotechnical Engineering and Environmental Engineering >Analysis of 220 kV Transformer Tripping Accident Caused by Neutral Point Gap Breakdown
【24h】

Analysis of 220 kV Transformer Tripping Accident Caused by Neutral Point Gap Breakdown

机译:中性点差距故障引起的220 kV变压器跳闸事故分析

获取原文

摘要

Through the neutral point of the main transformer is breakdown gap under the lightning over-voltage, and the main transformer is tripped by the zero-sequence protection, the discharge dispersion of gap is large is indicated; When 220 kV neutral point is ungrounded, the protection must be sharing after arrester parallel gap is proposed. The two-phase or three-phase wave is the main reason of the protection device action are pointed by discussing the wave process in the transformer; The most simple and effective way is placing special transparent insulating over the gap is proposed.
机译:通过主变压器的中性点是雷电过电压下的故障间隙,并且主变压器通过零序保护跳闸,表示间隙的放电分散量大;当220 kV中性点未接待时,在提出避雷器平行间隙后,必须共享保护。两相或三相波是通过讨论变压器中的波程来指向保护装置动作的主要原因;提出了最简单且有效的方法,提出了在间隙上放置特殊的透明绝缘。