Power transformers are designed to withstand switching and lightning overvoltages which can occur in the power system. The knowledge about waveshapes of these events grows rapidly with the introduction of online transient monitoring systems. Consequently, it is important to compare standard test voltage impulses with the ones existing in the power system. In this paper, 123 measured overvoltages in 220 kV air-insulated substation are analyzed. The observed overvoltages are fitted using double exponential mathematical function. Function parameters are calculated using genetic algorithm. To compare measured signals with the standard ones, statistical analysis of their parameters is performed. This approach can help in better dimensioning of the transformer insulation in order to withstand the real overvoltages that can occur in the power network and in avoiding potentially dangerous situation due to the resonances. Additionally, frequency domain severity factor is calculated for the observed signals.
机译:电力变压器设计用于承受在电力系统中发生的开关和避雷过电压。对这些事件的波浪的知识随着在线瞬态监测系统的引入而迅速增长。因此,重要的是将标准的测试电压脉冲与电力系统中存在的标准测试电压脉冲进行比较。在本文中,分析了220kV空气绝缘变电站中的123测量过电压。观察到的过电压使用双指数数学函数配合。使用遗传算法计算功能参数。为了将测量信号与标准值进行比较,执行其参数的统计分析。该方法可以帮助更好地尺寸变压器绝缘尺寸,以承受电力网络中可能发生的真正过电压,并且在避免由于共振引起的潜在危险情况。另外,为观察到的信号计算频域严重性因子。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号