首页> 外文会议>International Cryogenic Materials Conference >1 atm subcooled liquid nitrogen cryogenic system with GM-refrigerator for a HTS power transformer
【24h】

1 atm subcooled liquid nitrogen cryogenic system with GM-refrigerator for a HTS power transformer

机译:1个ATM过冷液氮低温系统,用于HTS电源变压器的GM-冰箱

获取原文

摘要

A subcooled liquid nitrogen cryogenic system with GM-refrigerators was developed. The system was operated successfully in a commercial distribution power grid for three consecutive weeks without additional liquid nitrogen supply. The system consists of two main units. One is a HTS transformer unit and the HTS transformer is installed in a G-FRP cryostat. The other one is a pump unit. The pump unit has a liquid nitrogen pump and two GM-refrigerators of 290 W at 64 K for 50 Hz operation in a stainless steel dewar. The refrigerator cold heads are immersed in liquid nitrogen and produce directly subcooled liquid nitrogen in the pump unit. Those two units are connected by transfer-tubes and 1 atmosphere (0.1 MPa) subcooled liquid nitrogen is circulated through the system. In the field test, the refrigerators were operated at 60 Hz and it took 12 hours to cool the transformer down to 70 K and 26 hours to 66 K. The refrigerator cold heads were controlled not to be below 64 K during operation. In spite of a heat generation by the HTS transformer, the subcooled liquid nitrogen temperature in the HTS transformer unit was kept lower than 68 K.
机译:开发了一种带通用冰箱的脱池液氮低温系统。该系统在商业分配电网中成功运行,连续三个周,没有额外的液氮供应。该系统由两个主要单位组成。一个是HTS变压器单元,HTS变压器安装在G-FRP低温恒温器中。另一个是泵单元。泵单元具有液氮泵和290W的290W的GM-冰箱,在64 k下,在不锈钢杜瓦尔的50 Hz操作。冰箱冷头浸入液氮中,在泵单元中产生直接过冷液氮。这两个单元通过转移管连接,1气氛(0.1MPa)过冷液氮通过系统循环。在现场试验中,冰箱在60 Hz下运行,需要12小时,将变压器冷却至70 k,26小时至66 k。在操作期间控制冰箱冷头不低于64 k。尽管HTS变压器由HTS变压器产生发热,但HTS变压器单元中的过冷液氮温度保持低于68k。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号